- In general cases, it is required to set 3 clamps in junction areas on the frames 3,30 m high. However, under conditions of high stretching load, especially on the corner areas and at the flank incasing, it is essential to put additional clamps on each junction. One additional clamp should be set when thickness of walls is not bigger then 40 cm and distance to the element junction 1,95 m from external corner or wall edge.
- Corner casing.
- Flank casing.
- Two additional clamps should be set when thickness of walls is not bigger then 60 cm and distance to the element junction 1,35 m from external corner or wall edge.
If element junctions is located on the distance of 1,35 m to 2,7 m from the external corner, it is essential to set one additional clamp.
Attention! In conditions of fresh concrete pressure more than 60 kN/m2 and wall thickness more than 40 cm it is essential to use cone bolts and clamping wedges instead of clamping devices.